Repair

Call for pricing
  • Usually ships in 3-5 business days

Remanufactured

Call for pricing
  • 1 in stock
  • IC610MDL176REP

Overview

Features

  • 97 to 265VAC operating voltage
  • 47 to 63Hz AC frequency
  • 2 Amps max. current
  • Max. leakage current:
    • 7mA @ 220V, 60Hz
    • 3.5mA @ 110V
  • 20 Amps max. inrush for 16ms
  • 0.8V @ 2 Amps ON voltage drop
  • 25mA smallest recommended load
  • 1.0ms OFF to ON response
  • 8 to 10ms ON to OFF response (1/2 cycle)
  • Logic side circuit indicator
  • (4) 3 Amp fast blow replaceable internal fuses (each circuit)
  • 12mA internal power consumption @ 9VDC
  • 8 units of load @ 9VDC

Description

The GE-Emerson IC610MDL176 Series One Isolated Output Module provides four circuits each capable of controlling user supplied discrete (ON/OFF) loads. Typical loads include relay coils, motor starters (up to No. 4), solenoid valves, and indicator lights. Each of these circuits is isolated from the other circuits on this module relative to the AC power source. The term isolation is not relative to optical-coupler noise and fault isolation, which all I/O modules have. Each output is provided with 2 field terminals allowing separate AC power sources (that is, different phases) for each of the 4 outputs. These power sources must be supplied by the user. Although this module consumes 8 discrete references assigned to the slot into which it is placed, only 4 are actually used. The other 4 can be used internally as coils, but thy cannot be provided to hardware I/O modules.