Features
- Inputs:
- Input voltage range: 0 to 132VAC
- Inputs per module: 8 (1 group of 8 inputs)
- Isolation:
- 1,500V RMS between field and logic side
- 500V RMS between inputs
- Input current: 12mA (typical) at rated voltage
- Outputs:
- Operating voltage:
- 5 to 30VDC
- 5 to 250VAC, 50/60Hz
- Outputs per module: 8 (2 groups of 4 outputs each)
- Isolation:
- 1,500V RMS between field and logic side
- 500V RMS between groups
- Maximum load:
- 2 Amps max. per output
- 4 Amps max. per common
- 10mA minimum load
- 5 Amps inrush
- 15ms maximum on/off response time
- Internal power consumption:
- 80mA (all I/O on) from 5V backplane bus
- 70mA (all outputs on) from relay 24V backplane bus
- Operating voltage:
Description
The GE-Emerson IC693MAR590 120 Volt AC Input and Relay Output Module for the Series 90-30 Programmable Logic Controller provides 8 input points with one common power input terminal, and 8 normally-open relay circuits in the same module. The input circuits are reactive (resistor/capacitor) inputs and are arranged as one group of 8 inputs. The output points are arranged in two groups of four points each. Each group has a common power output terminal.
Input characteristics are compatible with user-supplied devices such as pushbuttons, limit switches, and electronic proximity switches. Current through an input results in a logic 1 in the input status table (%I). Power to operate the field devices must be supplied by the user. This module's input section requires an AC power source, it cannot be used with a DC power source.
The normally-open relay circuits are used for controlling output loads provided by the user. The output switching capacity of each output is 2 Amps. The relay outputs can control a wide range of user-supplied load devices, such as motor starters, solenoids, and indicators. Power for the internal relay circuits is provided by the 24VDC bus on the backplane. The user must supply the AC or DC power to operate field devices. There are no fuses on this module.
Documents
Need Help? Call an expert at 1-704-702-6380
We're open Mo-Fr 8:00am to 5:00pm