Repair

$460.00
  • Usually ships in 3-5 business days

Remanufactured

$575.00
  • 4 in stock
  • Additional 50 ready to ship within 2-3 days

For on-site repair and support, call us at 1-704-448-2212 or email sales@qualitrol.com.

  • IC693MDL940REP

Overview

Features

  • 24VDC, 120/240VAC rated voltage (nominal)
  • Operating voltage:
    • 5 to 30VDC
    • 5 to 250VAC, 50/60Hz
  • Isolation:
    • 1,500V between field side and logic side
    • 500V between groups
  • Maximum load:
    • 2 Amps pilot duty max. per output
    • 4 Amps max. per common
  • 10mA minimum load
  • 5 Amps max. inrush
  • 15ms max. On and Off response time
  • Internal power consumption:
    • 7mA (all outputs on) from 5V bus on backplane
    • 135mA (all outputs on) from relay 24V bus on backplane

Description

The GE-Emerson IC693MDL940 2 Amp Relay Output Module can control a wide range of user-supplied load devices, such as motor starters, solenoids, and indicators. Power for the internal relay circuits is provided by the +24 volt  DC bus on the backplane. The user must supply the AC or DC power to operate field devices. There are no fuses on the module.

LED indicators that provide each point's ON/OFF status are located at the top of the module. The LEDs are arranged in two horizontal rows with eight green LEDs in each row; the top row labeled A1 through 8 (points 1 through 8) and the bottom row labeled B1 through 8 (points 9 through 16). An insert goes between the inside and outside surfaces of the hinged door. The surface towards the inside of the module (when the hinged door is closed) has circuit wiring information, and circuit identification information can be recorded on the outside surface. The outside left edge of the insert is color-coded red to indicate a high-voltage module. The module can be installed in any I/O slot of a 5 or 10-slot baseplate in a Series 90-30 PLC system.