Repair

Call for pricing
  • Usually ships in 2-3 weeks

Remanufactured

$250.00
  • Additional 1 ready to ship within 2-3 days
  • 1762-OF4REP

Overview

Features

  • 0 to 10VDC analog normal operating range
  • Max. bus current draw:
    • 40mA @ 5VDC
    • 165mA @ 24VDC
  • Full scale analog ranges:
    • Voltage: 0 to 10.5VDC
    • Current: 0 to 21mA
  • -0.12 to 0.12% repeatability
  • Input and output group to system isolation:
    • 30VAC/30VDC rated working voltage (IEC Class 2 reinforced insulation) type test: 500VAC or 707VDC for 1min
  • Screw electric connection
  • IEC1000-4-4: 2kV, 5kHz fast transient burst
  • 10V, 0.15 to 80MHz conducted immunity
  • Radiated immunity:
    • IEC1000-4-3: 10V/m, 80 to 1,000MHz, 80% amplitude modulation, +900MHz keyed carrier
  • IEC1000-4-5: 1kV galvanic gun surge immunity

Description

The Allen-Bradley 1762-OF4 MicroLogix 1200 Analog Output Module is designed to mount to a well-grounded surface, such as a metal panel, with no extra grounding connections required from the mounting tabs or DIN rail. The module provides analog output signals used to drive valves, VFDs, dampers, louvers, and other modulating control elements. The module can also re-transmit to indicators, data loggers, isolators, and converters. 

The module converts binary data from the CPU to analog signal via an internal Digital to Analog Circuit (DAC) with R-2R Ladder Voltage Switching. The module may assist in implementing automatic control of devices by being assigned as the output of a Proportional +Integral +Derivative (PID) controller. It may also be connected via HMI or SCADA to manual entry values such as manual loading stations.