Repair Allen-Bradley 1756-OA8 ControlLogix Digital AC Output Module
8 outputs, 4 points per group.
Remanufactured
-
1 in stock
- 1756-OA8REP
Overview
Features
- 2A pilot duty
- 120/240VAC (50/60Hz) voltage category
- Operating voltage range:
- 74 to 265VAC
- 47 to 63Hz
- Output delay time:
- OFF to ON:
- 9.3ms @ 60Hz
- 11ms @ 50Hz
- ON to OFF:
- 9.3ms @ 60Hz
- 11ms @ 50Hz
- OFF to ON:
- Current draw:
- 200mA @ 5.1V
- 2mA @ 24V
- 1.07W total backplane power
- 5.1W @ 140°F max. power dissipation
- 17.39 BTU/hr thermal dissipation
- 3mA per point max. off-state leakage current
- Max. on-state voltage drop:
- 1.5V peak @ 2A
- 6V peak @ <50mA
- 2A @ 140°F max. current per point, linear derating
- Max. current per module:
- 5A @ 86°F, linear derating
- 4A @ 140°F, linear derating
Description
The Allen-Bradley 1756-OA8 ControlLogix Digital AC Output Module includes States in Fault mode per point and States in Program mode per point that can hold the most recent state, for both on-state and off-state. While only AC voltage should be used, channels are grouped to allow each channel to be operated independently by the module at different AC voltage levels. An Allen-Bradley Removable Terminal Block (RTB) is required for the module.