Repair GE-Emerson IC220ALG220 VersaPoint Analog Voltage and Current Input Module
2 analog single-ended inputs, designed according to EN 61131-2, Type 1.
Remanufactured
-
4 in stock
- IC220ALG220REP
- By GE-Emerson
Overview
Features
- Voltage inputs:
- >220kΩ input resistance
- 40Hz limit frequency (-3dB) of the input filter
- <1.5ms process data update of both channels
- Goes to 0V upon sensor failure
- +/-32V max. permissible voltage between analog voltage inputs and analog reference potential
- 90dB min. common mode rejection (CMR); 110dB typical
- Permissible DC common mode voltage for CMR: 40V between voltage input and FE
- Current inputs:
- 50Ω (shunt) input resistance
- 40Hz limit frequency (-3dB) of the input filter
- <1.5ms process data update of both channels
- Goes to 0mA/4mA upon sensor failure
- +/-5V max. permissible voltage between analog voltage inputs and analog reference potential (corresponding with 100mA across the sensor resistances)
- 90dB min. common mode rejection (CMR); 110dB typical
- Permissible DC common mode voltage for CMR: 40V between voltage input and FE
- +/-100mA max. permissible current
Description
The GE-Emerson IC220ALG220 VersaPoint Analog Voltage and Current Input Module is used to measure analog voltage or current signals. The module requires one I/O terminal strip, sold separately. Two analog single-ended inputs for either voltage or current signals are included, allowing the connection of 2- and 3-wire sensors. Configuration of the independent channels is provided, and measured values can be represented in two formats. Resolution is independent of representation format and measuring range. Diagnostic indicators are included. To provide electrical isolation between the logic level and the I/O area it is necessary to supply the bus module and the sensors using a power terminal from separate power supplies. Interconnection of power supply units in the 24V range is not allowed.