Features
- 180 to 265VAC operating voltage
- 47 to 63Hz AC frequency
- 80mA max. input current (265V, 60Hz)
- 11mA typical input current
- 18K ohms input impedance @ 60Hz
- ON voltage: above 180VAC
- OFF voltage: below 40VAC
- OFF current: <2mA
- OFF to ON response: 5 to 50ms
- ON to OFF response: 5 to 60ms
- Field side circuit indicators
- 10mA, 9VDC internal power consumption
- 1 unit of load @ 9VDC
Description
The GE-Emerson IC610MDL127 Series One Input Module provides circuits each designed to receive a single discrete (ON/OFF) signal from user supplied devices. Typical input devices include limit switches, pushbuttons, selector switches, and relay contacts. The 8 circuits are divided into two groups of 4 circuits each. Each of the 2 groups can be supplied from a separate power source. Power to operate the field devices must also be supplied by the user.