Repair

Call for pricing
  • Usually ships in 3-5 business days

Remanufactured

Call for pricing
  • 10 in stock
  • IC610MDL153REP

Overview

Features

  • 5 to 24VDC operating voltage
  • 45VDC peak voltage
  • ON voltage drop:
    • 0.15VDC @ 1 Amps
    • 0.6VDC @ 4 Amps
  • 2 Amps max. current
  • <0.4mA @ 40VDC max. leakage current
  • 0.1ms OFF to ON and ON to OFF response
  • Logic side circuit indicator
  • 5 Amp replaceable internal fuses (1 for each circuit)
  • Internal power consumption:
    • 5mA @ 24VDC
    • 12mA @ 9VDC
  • Units of load:
    • 1 unit @ 24VDC
    • 2 units @ 9VDC

Description

The GE-Emerson IC610MDL153 Series One Sink Output Module provides fused output circuits each capable of controlling user supplied discrete (ON/OFF) loads. Each circuit is rated at 2 Amps continuous current. Typical loads include motor starters, relay coils, solenoid valves, and indicator lights. The circuits on this module are referred to as sink outputs, since current flows from the load into the field terminal for each circuit when the output is energized. Field connections are made to screw terminals on a terminal block mounted on the faceplate. Each terminal will accept up to one No. 12 AWG wire or two No. 14 AWG wires. The ON/OFF state of each circuit is indicated by a corresponding LED. This module, although having only 4 output circuits, will consume 8 consecutive discrete references. The 4 references not available as "real world" outputs can be used as internal coils.